App Overview
This cable enhances circuit integrity over cables with the same rated power, it is mainly used in installations where there is critical circuitry needed to maintain continuous operation in the event of a fire. . Fireproof cable is suitable for use in other public works such as shopping malls, hospitals, theaters, public transport…
Flame Retardant Cable Specifications
Cable Specifications CU/PVC600/1000 V
Applied standard
OVI power cables are completely manufactured according to the following standards:
BS 6387 : Capability requirements for cables to protect circuit integrity
IEC 60331 : Fire resistance characteristics of insulated cables
IEC 60332-1 : Flame retardancy characteristics of electric cables
IEC 60332-3 : Testing of electrical cables under fire conditions part 3: Tests on cables or cords
Identify the wire
– Conductor : Braided round copper core (layer 2)
– Insulation: Blue, red, yellow, black, green combined with yellow (Te) or as required.
– Cover: orange or as required
Specifications
1 CORE CU/MICA/LSHF or PVC_FR 600/1000V
Nominal area | Approx. overall diameter |
Caculated Aprrox cable weight |
Minimum bending radius |
Test Voltage |
Max. conductor DC resistance at 200C |
Current rating based on free air at 250C |
Current rating based on free air at 300C |
Volt drop for 3 phase circuit |
(mm2) | (mm) | (Kg/km) | (mm) | (kV/5min) | (Ω/km) | (Amp) | (Amp) | (V/A/km) |
1.5 | 3.9 | 29 | 24 | 3.5 | 12.1 | 23 | 19 | 27.0 |
2.5 | 4.3 | 40 | 26 | 3.5 | 7.41 | 32 | 26 | 16.0 |
4 | 4.8 | 61 | 28 | 3.5 | 4.61 | 42 | 35 | 10.0 |
6 | 5.4 | 83 | 30 | 3.5 | 3.08 | 55 | 45 | 6.8 |
10 | 6.3 | 126 | 33 | 3.5 | 1.83 | 75 | 63 | 4.0 |
16 | 7.9 | 184 | 63 | 3.5 | 1.15 | 83 | 81 | 2.40 |
25 | 9.5 | 284 | 76 | 3.5 | 0.727 | 110 | 107 | 1.55 |
35 | 10.4 | 405 | 83 | 3.5 | 0.524 | 137 | 134 | 1.10 |
50 | 12.1 | 509 | 97 | 3.5 | 0.387 | 167 | 163 | 0.84 |
70 | 13.6 | 709 | 109 | 3.5 | 0.268 | 216 | 211 | 0.60 |
95 | 15.8 | 974 | 126 | 3.5 | 0.193 | 264 | 257 | 0.47 |
120 | 17.0 | 1221 | 136 | 3.5 | 0.153 | 308 | 300 | 0.40 |
150 | 19.6 | 1485 | 157 | 3.5 | 0.124 | 356 | 347 | 0.34 |
1 CORE CU/MICA/XLPE/LSHF or PVC_FR 600/1000V
Nominal area | Approx. overall diameter |
Caculated Aprrox cable weight |
Minimum bending radius |
Test Voltage |
Max. conductor DC resistance at 200C |
Current rating based on free air at 250C |
Current rating based on free air at 300C |
Volt drop for 3 phase circuit |
(mm2) | (mm) | (Kg/km) | (mm) | (kV/5min) | (Ω/km) | (Amp) | (Amp) | (V/A/km) |
1.5 | 6.8 | 61 | 54 | 3.5 | 12.1 | 30 | 26 | 31 |
2.5 | 7.2 | 74 | 58 | 3.5 | 7.41 | 40 | 35 | 19 |
4 | 7.8 | 94 | 62 | 3.5 | 4.61 | 53 | 46 | 12 |
6 | 8.3 | 118 | 66 | 3.5 | 3.08 | 68 | 59 | 7.9 |
10 | 9.3 | 164 | 74 | 3.5 | 1.83 | 93 | 81 | 4.7 |
16 | 9.6 | 223 | 77 | 3.5 | 1.15 | 101 | 88 | 2.55 |
25 | 11.3 | 326 | 90 | 3.5 | 0.727 | 133 | 138 | 1.60 |
35 | 12.5 | 427 | 100 | 3.5 | 0.524 | 164 | 171 | 1.15 |
50 | 13.9 | 556 | 111 | 3.5 | 0.387 | 213 | 209 | 0.87 |
70 | 16.0 | 769 | 128 | 3.5 | 0.268 | 273 | 270 | 0.61 |
95 | 17.8 | 1036 | 143 | 3.5 | 0.193 | 333 | 330 | 0.45 |
120 | 19.8 | 1269 | 158 | 3.5 | 0.153 | 387 | 385 | 0.37 |
150 | 21.6 | 1564 | 173 | 3.5 | 0.124 | 445 | 445 | 0.31 |
185 | 24.1 | 1936 | 192 | 3.5 | 0.0991 | 510 | 511 | 0.26 |
240 | 27.0 | 2481 | 216 | 3.5 | 0.0754 | 602 | 606 | 0.22 |
300 | 29.7 | 3144 | 238 | 3.5 | 0.0601 | 695 | 701 | 0.195 |
400 | 33.1 | 3993 | 265 | 3.5 | 0.0470 | 809 | 820 | 0.175 |
500 | 36.8 | 4995 | 294 | 3.5 | 0.0366 | 922 | 936 | 0.16 |
630 | 41.3 | 6592 | 330 | 3.5 | 0.0283 | 1054 | 1069 | 0.15 |
2 CORE CU/MICA/XLPE/LSHF or PVC_FR 600/1000V
Nominal area | Approx. overall diameter |
Caculated Aprrox cable weight |
Minimum bending radius |
Test Voltage |
Max. conductor DC resistance at 200C |
Current rating based on free air at 250C |
Current rating based on free air at 300C |
Volt drop for 3 phase circuit |
(mm2) | (mm) | (Kg/km) | (mm) | (kV/5min) | (Ω/km) | (Amp) | (Amp) | (V/A/km) |
1.5 | 10.9 | 156 | 66 | 3.5 | 12.1 | 22.4 | 26 | 31 |
2.5 | 11.8 | 186 | 71 | 3.5 | 7.41 | 31 | 36 | 19 |
4 | 12.8 | 233 | 77 | 3.5 | 4.61 | 41 | 49 | 12 |
6 | 14.0 | 289 | 84 | 3.5 | 3.08 | 52 | 63 | 7.9 |
10 | 15.8 | 397 | 95 | 3.5 | 1.83 | 70 | 86 | 4.7 |
16 | 17.5 | 532 | 105 | 3.5 | 1.15 | 93 | 115 | 2.9 |
25 | 16.8 | 768 | 101 | 3.5 | 0.727 | 121 | 149 | 1.9 |
35 | 18.5 | 995 | 148 | 3.5 | 0.524 | 149 | 185 | 1.35 |
50 | 21.1 | 1286 | 168 | 3.5 | 0.387 | 179 | 225 | 1.00 |
70 | 23.9 | 1778 | 191 | 3.5 | 0.268 | 225 | 289 | 0.69 |
95 | 26.4 | 2369 | 211 | 3.5 | 0.193 | 270 | 352 | 0.52 |
120 | 29.3 | 2893 | 234 | 3.5 | 0.153 | 311 | 410 | 0.42 |
150 | 32.7 | 3602 | 261 | 3.5 | 0.124 | 341 | 473 | 0.35 |
185 | 36.2 | 4441 | 290 | 3.5 | 0.0991 | 392 | 542 | 0.29 |
240 | 40.5 | 5682 | 324 | 3.5 | 0.0754 | 468 | 641 | 0.24 |
300 | 44.5 | 7113 | 356 | 3.5 | 0.0601 | 543 | 741 | 0.21 |
400 | 50.7 | 9084 | 406 | 3.5 | 0.0470 | 638 | 865 | 0.19 |
3 CORE CU/MICA/XLPE/LSHF or PVC_FR 600/1000V
Nominal area | Approx. overall diameter |
Caculated Aprrox cable weight |
Minimum bending radius |
Test Voltage |
Max. conductor DC resistance at 200C |
Current rating based on free air at 250C |
Current rating based on free air at 300C |
Volt drop for 3 phase circuit |
(mm2) | (mm) | (Kg/km) | (mm) | (kV/5min) | (Ω/km) | (Amp) | (Amp) | (V/A/km) |
1.5 | 11.5 | 183 | 69 | 3.5 | 12.1 | 20 | 23 | 26.83 |
2.5 | 12.4 | 224 | 74 | 3.5 | 7.41 | 27 | 32 | 16.42 |
4 | 13.6 | 285 | 81 | 3.5 | 4.61 | 36 | 42 | 10.22 |
6 | 14.8 | 361 | 89 | 3.5 | 3.08 | 45 | 54 | 6.83 |
10 | 16.8 | 509 | 101 | 3.5 | 1.83 | 61 | 75 | 4.06 |
16 | 18.6 | 699 | 112 | 3.5 | 1.15 | 82 | 100 | 2.55 |
25 | 19.2 | 1026 | 115 | 3.5 | 0.727 | 107 | 127 | 1.61 |
35 | 21.3 | 1344 | 170 | 3.5 | 0.524 | 131 | 158 | 1.17 |
50 | 24.3 | 1752 | 195 | 3.5 | 0.387 | 157 | 192 | 0.87 |
70 | 27.7 | 2456 | 222 | 3.5 | 0.268 | 198 | 246 | 0.61 |
95 | 21.3 | 3291 | 250 | 3.5 | 0.193 | 238 | 298 | 0.45 |
120 | 34.7 | 4024 | 277 | 3.5 | 0.153 | 273 | 346 | 0.37 |
150 | 38.7 | 5008 | 309 | 3.5 | 0.124 | 306 | 399 | 0.31 |
185 | 42.8 | 6184 | 343 | 3.5 | 0.0991 | 347 | 456 | 0.26 |
240 | 48.0 | 7930 | 384 | 3.5 | 0.0754 | 406 | 538 | 0.21 |
300 | 53.0 | 10013 | 424 | 3.5 | 0.0601 | 464 | 621 | 0.19 |
400 | 60.3 | 12745 | 483 | 3.5 | 0.047 | 547 | 741 | 0.17 |
4 CORE CU/MICA/XLPE/LSHF or PVC_FR 600/1000V
Nominal area | Approx. overall diameter |
Caculated Aprrox cable weight |
Minimum bending radius |
Test Voltage |
Max. conductor DC resistance at 200C |
Current rating based on free air at 250C |
Current rating based on free air at 300C |
Volt drop for 3 phase circuit |
(mm2) | (mm) | (Kg/km) | (mm) | (kV/5min) | (Ω/km) | (Amp) | (Amp) | (V/A/km) |
1.5 | 12.4 | 217 | 74 | 3.5 | 12.1 | 22.4 | 23 | 27 |
2.5 | 13.4 | 269 | 80 | 3.5 | 7.41 | 31 | 32 | 16 |
4 | 14.7 | 348 | 118 | 3.5 | 4.61 | 41 | 42 | 10 |
6 | 16.1 | 445 | 129 | 3.5 | 3.08 | 53 | 54 | 6.8 |
10 | 18.4 | 637 | 147 | 3.5 | 1.83 | 72 | 75 | 4.0 |
16 | 20.4 | 885 | 122 | 3.5 | 1.15 | 98 | 100 | 2.5 |
25 | 21.5 | 1310 | 129 | 3.5 | 0.727 | 121 | 127 | 1.65 |
35 | 23.9 | 1725 | 191 | 3.5 | 0.524 | 150 | 158 | 1.15 |
50 | 27.4 | 2273 | 219 | 3.5 | 0.387 | 183 | 192 | 0.87 |
70 | 31.7 | 3192 | 254 | 3.5 | 0.268 | 234 | 246 | 0.60 |
95 | 35.6 | 4285 | 284 | 3.5 | 0.193 | 284 | 298 | 0.45 |
120 | 39.4 | 5265 | 315 | 3.5 | 0.153 | 328 | 346 | 0.37 |
150 | 44.2 | 6525 | 354 | 3.5 | 0.124 | 378 | 399 | 0.30 |
185 | 49.0 | 8091 | 392 | 3.5 | 0.0991 | 432 | 456 | 0.26 |
240 | 54.8 | 10378 | 439 | 3.5 | 0.0754 | 510 | 538 | 0.21 |
300 | 60.5 | 13119 | 489 | 3.5 | 0.0601 | 588 | 621 | 0.185 |
400 | 69.2 | 16734 | 553 | 3.5 | 0.0470 | 638 | 741 | 0.165 |