Soft civil wires
STANDARDS APPLY
•TCVN 6610-5/IEC 60227-5
•TCVN 6612 / IEC 60228
•JIS C 3307; JIS C 3102
•AS/NZS 5000.1; AS/NZS 1125
PVC coated copper conductor (with or without sheath) used for civil electrical equipment.
This product is installed in pipes (bearing, leakproof…) at the following locations:
Fixed mounting on the wall, on the ceiling, on the floor.
Install sound in the wall, in the ceiling, in the floor.
Or buried in the ground.
App Overview
PVC coated copper conductor (with or without sheath) used for civil electrical equipment.
This product is mounted in a tube , Fixed mounting on the wall, on the ceiling, on the floor.
Install sound in the wall, in the ceiling, in the floor.
Or buried in the ground.
Cable Specifications CU/PVC 450/750 V
Cable Specifications CU/PVC600/1000 V
Applied standard
- Applicable standards: TCVN 6612
- TCVN 6610-3; TCVN 6610-5
-
Voltage: 300/500 V; 450/750 V
Identify the wire
– Conductor : Braided round copper core (layer 2)
– Insulation: Blue, red, yellow, black, green combined with yellow (Te) or as required.
All civil cables are manufactured according to the following standards:
Single flexible civil wire (VCm): TCVN 6610-3/IEC 60227-3
Flat double flexible civil cord (VCmD): AS/NZS 5000.1
Oval flexible double civil wire (VcmO): TCVN 6610-5/IEC 60227-5
Cable structure
Specifications
Nominal area |
Conductor diameter |
Thickness of insulation | Approx. overall diameter |
Caculated Approx. weight |
DC resistance at 200C |
Current rating based on clipped direct at 250C | Current rating based on drawn into duct at 250C |
1.5 | 1.6 | 0.70 | 3.0 | 24 | 12.1 | 18.5 | 16 |
2.5 | 2.0 | 0.80 | 3.6 | 36 | 7.41 | 25.8 | 21.6 |
4 | 2.6 | 0.80 | 4.2 | 52 | 4.61 | 34 | 28.8 |
6 | 3.1 | 0.80 | 4.7 | 73 | 3.08 | 44.3 | 37.1 |
10 | 4.1 | 1.00 | 6.1 | 120 | 1.83 | 60.8 | 51.5 |