Medium voltage cable
STANDARDS APPLY
OVI power cables are completely manufactured according to the following standards:
TCVN 6612: 2007 (IEC 60228), TCVN 5935: 2013 (IEC 60502-1)
App Overview
Used to transmit electricity with high voltage, install overhead power transmission lines, in ladders, cable trays or underground
Specifications of medium voltage underground cable
Cable Specifications CU/PVC600/1000 V
Applied standard
TCVN 6612 : 2007 (IEC 60228), TCVN 5935 -2: 2013 (IEC 60502-12
Identify the wire
– Conductor : Braided round copper core (layer 2)
– Insulation: Green, red, yellow, or as required
– Cover: Black or as required
Specifications
CU/XLPE/PVC, 3 COPPER LEADERS, UNARRATED 3.6/6 (7.2) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 2.50 | 2.20 | 38.0 | 0.524 | 2044 |
3 x 50 | 8.2 | 2.50 | 2.30 | 40.5 | 0.387 | 2485 |
3 x 70 | 9.8 | 2.50 | 2.40 | 44.3 | 0.268 | 3212 |
3 x 95 | 11.6 | 2.50 | 2.50 | 48.4 | 0.193 | 4106 |
3 x 120 | 13.0 | 2.50 | 2.60 | 51.7 | 0.153 | 4922 |
3 x 150 | 14.3 | 2.50 | 2.70 | 54.6 | 0.124 | 5804 |
3 x 185 | 16.0 | 2.50 | 2.80 | 58.5 | 0.0991 | 6981 |
3 x 240 | 18.3 | 2.60 | 3.00 | 64.4 | 0.0754 | 8839 |
3 x 300 | 20.5 | 2.80 | 3.20 | 70.4 | 0.0601 | 10853 |
3 x 400 | 23.2 | 3.00 | 3.50 | 77.6 | 0.0470 | 13580 |
CU/XLPE/PVC, 1 COPPER LEAD, UNARRATED 3.6/6 (7.2) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 2.50 | 1.80 | 19.1 | 0.524 | 640 |
1 x 50 | 8.2 | 2.50 | 1.80 | 20.2 | 0.387 | 772 |
1 x 70 | 9.8 | 2.50 | 1.80 | 21.8 | 0.268 | 992 |
1 x 95 | 11.6 | 2.50 | 1.80 | 23.6 | 0.193 | 1262 |
1 x 120 | 13.0 | 2.50 | 1.80 | 25.0 | 0.153 | 1508 |
1 x 150 | 14.3 | 2.50 | 1.80 | 26.3 | 0.124 | 1778 |
1 x 185 | 16.0 | 2.50 | 1.90 | 28.1 | 0.0991 | 2142 |
1 x 240 | 18.3 | 2.60 | 1.90 | 30.8 | 0.0754 | 2716 |
1 x 300 | 20.5 | 2.80 | 2.00 | 33.6 | 0.0601 | 3336 |
1 x 400 | 23.2 | 3.00 | 2.20 | 36.9 | 0.0470 | 4176 |
1 x 500 | 26.3 | 3.20 | 2.30 | 40.6 | 0.0366 | 5250 |
1 x 600 | 28.8 | 3.20 | 2.30 | 43.3 | 0.0305 | 6191 |
1 x 630 | 29.9 | 3.20 | 2.40 | 44.5 | 0.0283 | 6625 |
CU/XLPE/PVC/DSTA/PVC, 3 COPPER LEADERS, STEEL FEATURE Armor 3.6/6 (7.2) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of steel tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 2.50 | 0.50 | 2.30 | 43.1 | 0.524 | 3057 |
3 x 50 | 8.2 | 2.50 | 0.50 | 2.40 | 45.8 | 0.387 | 3574 |
3 x 70 | 9.8 | 2.50 | 0.50 | 2.50 | 49.7 | 0.268 | 4419 |
3 x 95 | 11.6 | 2.50 | 0.50 | 2.70 | 53.9 | 0.193 | 5449 |
3 x 120 | 13.0 | 2.50 | 0.50 | 2.80 | 57.3 | 0.153 | 6378 |
3 x 150 | 14.3 | 2.50 | 0.50 | 2.90 | 60.4 | 0.124 | 7356 |
3 x 185 | 16.0 | 2.50 | 0.50 | 3.00 | 64.5 | 0.0991 | 8670 |
3 x 240 | 18.3 | 2.60 | 0.50 | 3.20 | 70.5 | 0.0754 | 10731 |
3 x 300 | 20.5 | 2.80 | 0.50 | 3.40 | 76.8 | 0.0601 | 12971 |
3 x 400 | 23.2 | 3.00 | 0.80 | 3.70 | 85.6 | 0.0470 | 16865 |
CU/XLPE/PVC/DATA/PVC, 1 COPPER ELECTRIC, ALUMINUM FEATURE 3.6/6 (7.2) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of Aluminium tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 2.50 | 0.50 | 1.80 | 23.7 | 0.524 | 906 |
1 x 50 | 8.2 | 2.50 | 0.50 | 1.80 | 24.8 | 0.387 | 1052 |
1 x 70 | 9.8 | 2.50 | 0.50 | 1.80 | 26.5 | 0.268 | 1293 |
1 x 95 | 11.6 | 2.50 | 0.50 | 1.90 | 28.4 | 0.193 | 1592 |
1 x 120 | 13.0 | 2.50 | 0.50 | 1.90 | 29.9 | 0.153 | 1863 |
1 x 150 | 14.3 | 2.50 | 0.50 | 2.00 | 31.3 | 0.124 | 2155 |
1 x 185 | 16.0 | 2.50 | 0.50 | 2.00 | 33.1 | 0.0991 | 2543 |
1 x 240 | 18.3 | 2.60 | 0.50 | 2.10 | 35.8 | 0.0754 | 3152 |
1 x 300 | 20.5 | 2.80 | 0.50 | 2.20 | 38.6 | 0.0601 | 3808 |
1 x 400 | 23.2 | 3.00 | 0.50 | 2.30 | 42.0 | 0.0470 | 4704 |
1 x 500 | 26.3 | 3.20 | 0.50 | 2.40 | 45.9 | 0.0366 | 5842 |
1 x 600 | 28.8 | 3.20 | 0.50 | 2.50 | 48.6 | 0.0305 | 6831 |
1 x 630 | 29.9 | 3.20 | 0.50 | 2.50 | 49.8 | 0.0283 | 7285 |
CU/XLPE/PVC/SWA/PVC, 3 COPPER LEADERS, STEEL FIBER Armor 3.6/6 (7.2) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of steel wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 2.50 | 2.50 | 2.40 | 44.9 | 0.524 | 4120 |
3 x 50 | 8.2 | 2.50 | 2.50 | 2.50 | 47.7 | 0.387 | 4704 |
3 x 70 | 9.8 | 2.50 | 2.50 | 2.70 | 51.6 | 0.268 | 5661 |
3 x 95 | 11.6 | 2.50 | 2.50 | 2.80 | 55.8 | 0.193 | 6794 |
3 x 120 | 13.0 | 2.50 | 2.50 | 2.90 | 59.2 | 0.153 | 7803 |
3 x 150 | 14.3 | 2.50 | 2.50 | 3.00 | 62.3 | 0.124 | 8840 |
3 x 185 | 16.0 | 2.50 | 2.50 | 3.10 | 66.3 | 0.0991 | 10258 |
3 x 240 | 18.3 | 2.60 | 3.15 | 3.40 | 73.8 | 0.0754 | 13320 |
3 x 300 | 20.5 | 2.80 | 3.15 | 3.60 | 80.0 | 0.0601 | 15791 |
3 x 400 | 23.2 | 3.00 | 3.15 | 3.80 | 87.5 | 0.0470 | 19075 |
CU/XLPE/PVC/AWA/PVC, 1 COLLECTOR, ALUMINUM FIBER Armor 3.6/6 (7.2) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of aluminium wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 2.50 | 1.60 | 1.80 | 24.5 | 0.524 | 956 |
1 x 50 | 8.2 | 2.50 | 1.60 | 1.80 | 25.6 | 0.387 | 1103 |
1 x 70 | 9.8 | 2.50 | 1.60 | 1.90 | 27.3 | 0.268 | 1352 |
1 x 95 | 11.6 | 2.50 | 1.60 | 1.90 | 29.2 | 0.193 | 1659 |
1 x 120 | 13.0 | 2.50 | 1.60 | 2.00 | 30.7 | 0.153 | 1935 |
1 x 150 | 14.3 | 2.50 | 2.00 | 2.00 | 32.9 | 0.124 | 2312 |
1 x 185 | 16.0 | 2.50 | 2.00 | 2.10 | 34.7 | 0.0991 | 2713 |
1 x 240 | 18.3 | 2.60 | 2.00 | 2.20 | 37.4 | 0.0754 | 3336 |
1 x 300 | 20.5 | 2.80 | 2.00 | 2.30 | 40.2 | 0.0601 | 4004 |
1 x 400 | 23.2 | 3.00 | 2.50 | 2.40 | 44.7 | 0.0470 | 5065 |
1 x 500 | 26.3 | 3.20 | 2.50 | 2.50 | 48.6 | 0.0366 | 6228 |
1 x 600 | 28.8 | 3.20 | 2.50 | 2.60 | 51.3 | 0.0305 | 7251 |
1 x 630 | 29.9 | 3.20 | 2.50 | 2.60 | 52.5 | 0.0283 | 7710 |
CU/XLPE/PVC, 3 COPPER LEADERS, UNARRATED 6/10 (12) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 3.40 | 2.30 | 42.2 | 0.524 | 2313 |
3 x 50 | 8.2 | 3.40 | 2.40 | 44.8 | 0.387 | 2769 |
3 x 70 | 9.8 | 3.40 | 2.50 | 48.6 | 0.268 | 3521 |
3 x 95 | 11.6 | 3.40 | 2.70 | 52.6 | 0.193 | 4437 |
3 x 120 | 13.0 | 3.40 | 2.80 | 55.9 | 0.153 | 5273 |
3 x 150 | 14.3 | 3.40 | 2.90 | 58.9 | 0.124 | 6173 |
3 x 185 | 16.0 | 3.40 | 3.00 | 62.8 | 0.0991 | 7373 |
3 x 240 | 18.3 | 3.40 | 3.10 | 68.2 | 0.0754 | 9218 |
3 x 300 | 20.5 | 3.40 | 3.30 | 73.2 | 0.0601 | 11157 |
3 x 400 | 23.2 | 3.40 | 3.50 | 79.5 | 0.0470 | 13803 |
CU/XLPE/PVC, 1 COPPER LEAD, UNARRATED 6/10 (12) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 3.40 | 1.80 | 20.9 | 0.524 | 706 |
1 x 50 | 8.2 | 3.40 | 1.80 | 22.0 | 0.387 | 841 |
1 x 70 | 9.8 | 3.40 | 1.80 | 23.7 | 0.268 | 1065 |
1 x 95 | 11.6 | 3.40 | 1.80 | 25.4 | 0.193 | 1339 |
1 x 120 | 13.0 | 3.40 | 1.80 | 26.9 | 0.153 | 1593 |
1 x 150 | 14.3 | 3.40 | 1.90 | 28.3 | 0.124 | 1871 |
1 x 185 | 16.0 | 3.40 | 1.90 | 30.1 | 0.0991 | 2242 |
1 x 240 | 18.3 | 3.40 | 2.00 | 32.6 | 0.0754 | 2812 |
1 x 300 | 20.5 | 3.40 | 2.10 | 34.9 | 0.0601 | 3412 |
1 x 400 | 23.2 | 3.40 | 2.20 | 37.8 | 0.0470 | 4231 |
1 x 500 | 26.3 | 3.40 | 2.30 | 41.1 | 0.0366 | 5281 |
1 x 600 | 28.8 | 3.40 | 2.40 | 43.8 | 0.0305 | 6224 |
1 x 630 | 29.9 | 3.40 | 2.40 | 44.9 | 0.0283 | 6659 |
CU/XLPE/PVC/DSTA/PVC, 3 COPPER LEADERS, 6/10 (12) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of steel tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 3.40 | 0.50 | 2.50 | 47.5 | 0.524 | 3429 |
3 x 50 | 8.2 | 3.40 | 0.50 | 2.60 | 50.2 | 0.387 | 3965 |
3 x 70 | 9.8 | 3.40 | 0.50 | 2.70 | 54.2 | 0.268 | 4833 |
3 x 95 | 11.6 | 3.40 | 0.50 | 2.80 | 58.3 | 0.193 | 5874 |
3 x 120 | 13.0 | 3.40 | 0.50 | 2.90 | 61.8 | 0.153 | 6815 |
3 x 150 | 14.3 | 3.40 | 0.50 | 3.10 | 64.9 | 0.124 | 7814 |
3 x 185 | 16.0 | 3.40 | 0.50 | 3.20 | 68.9 | 0.0991 | 9141 |
3 x 240 | 18.3 | 3.40 | 0.50 | 3.30 | 74.5 | 0.0754 | 11169 |
3 x 300 | 20.5 | 3.40 | 0.50 | 3.50 | 79.8 | 0.0601 | 13285 |
3 x 400 | 23.2 | 3.40 | 0.80 | 3.80 | 87.6 | 0.0470 | 17063 |
CU/XLPE/PVC/DATA/PVC, 1 COPPER LEAD, 6/10 (12) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of Aluminium tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 3.40 | 0.50 | 1.80 | 25.6 | 0.524 | 995 |
1 x 50 | 8.2 | 3.40 | 0.50 | 1.80 | 26.7 | 0.387 | 1146 |
1 x 70 | 9.8 | 3.40 | 0.50 | 1.90 | 28.5 | 0.268 | 1397 |
1 x 95 | 11.6 | 3.40 | 0.50 | 1.90 | 30.3 | 0.193 | 1702 |
1 x 120 | 13.0 | 3.40 | 0.50 | 2.00 | 31.9 | 0.153 | 1978 |
1 x 150 | 14.3 | 3.40 | 0.50 | 2.00 | 33.2 | 0.124 | 2274 |
1 x 185 | 16.0 | 3.40 | 0.50 | 2.10 | 35.0 | 0.0991 | 2668 |
1 x 240 | 18.3 | 3.40 | 0.50 | 2.20 | 37.5 | 0.0754 | 3271 |
1 x 300 | 20.5 | 3.40 | 0.50 | 2.20 | 39.9 | 0.0601 | 3904 |
1 x 400 | 23.2 | 3.40 | 0.50 | 2.30 | 42.9 | 0.0470 | 4775 |
1 x 500 | 26.3 | 3.40 | 0.50 | 2.40 | 46.3 | 0.0366 | 5881 |
1 x 600 | 28.8 | 3.40 | 0.50 | 2.50 | 49.1 | 0.0305 | 6872 |
1 x 630 | 29.9 | 3.40 | 0.50 | 2.50 | 50.3 | 0.0283 | 7327 |
CU/XLPE/PVC/SWA/PVC, 3 COPPER LEADERS, STEEL FIBER Armor 6/10 (12) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of steel wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 3.40 | 2.50 | 2.60 | 49.3 | 0.524 | 4620 |
3 x 50 | 8.2 | 3.40 | 2.50 | 2.70 | 52.0 | 0.387 | 5221 |
3 x 70 | 9.8 | 3.40 | 2.50 | 2.80 | 55.9 | 0.268 | 6209 |
3 x 95 | 11.6 | 3.40 | 2.50 | 2.90 | 60.1 | 0.193 | 7363 |
3 x 120 | 13.0 | 3.40 | 2.50 | 3.00 | 63.5 | 0.153 | 8395 |
3 x 150 | 14.3 | 3.40 | 2.50 | 3.20 | 66.6 | 0.124 | 9451 |
3 x 185 | 16.0 | 3.40 | 2.50 | 3.30 | 70.6 | 0.0991 | 10895 |
3 x 240 | 18.3 | 3.40 | 3.15 | 3.50 | 77.6 | 0.0754 | 13996 |
3 x 300 | 20.5 | 3.40 | 3.15 | 3.70 | 82.9 | 0.0601 | 16322 |
3 x 400 | 23.2 | 3.40 | 3.15 | 3.90 | 89.4 | 0.0470 | 19450 |
CU/XLPE/PVC/AWA/PVC, 1 COPPER LEAD, ALUMINUM FIBER Armor 6/10 (12) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of aluminium wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 3.40 | 1.60 | 1.80 | 26.3 | 0.524 | 1052 |
1 x 50 | 8.2 | 3.40 | 1.60 | 1.90 | 27.5 | 0.387 | 1208 |
1 x 70 | 9.8 | 3.40 | 1.60 | 1.90 | 29.2 | 0.268 | 1462 |
1 x 95 | 11.6 | 3.40 | 1.60 | 2.00 | 31.1 | 0.193 | 1769 |
1 x 120 | 13.0 | 3.40 | 1.60 | 2.00 | 33.5 | 0.153 | 2137 |
1 x 150 | 14.3 | 3.40 | 2.00 | 2.10 | 34.9 | 0.124 | 2441 |
1 x 185 | 16.0 | 3.40 | 2.00 | 2.10 | 36.7 | 0.0991 | 2847 |
1 x 240 | 18.3 | 3.40 | 2.00 | 2.20 | 39.1 | 0.0754 | 3456 |
1 x 300 | 20.5 | 3.40 | 2.00 | 2.30 | 41.5 | 0.0601 | 4107 |
1 x 400 | 23.2 | 3.40 | 2.50 | 2.40 | 45.6 | 0.0470 | 5141 |
1 x 500 | 26.3 | 3.40 | 2.50 | 2.50 | 49.0 | 0.0366 | 6276 |
1 x 600 | 28.8 | 3.40 | 2.50 | 2.60 | 51.8 | 0.0305 | 7287 |
1 x 630 | 29.9 | 3.40 | 2.50 | 2.70 | 52.9 | 0.0283 | 7760 |
CU/XLPE/PVC/AWA/PVC, 1 COPPER LEAD, ALUMINUM FIBER Armor 6/10 (12) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 5.50 | 2.60 | 52.1 | 0.524 | 3039 |
3 x 50 | 8.2 | 5.50 | 2.70 | 54.7 | 0.387 | 3533 |
3 x 70 | 9.8 | 5.50 | 2.80 | 58.5 | 0.268 | 4335 |
3 x 95 | 11.6 | 5.50 | 3.00 | 65.5 | 0.193 | 5307 |
3 x 120 | 13.0 | 5.50 | 3.10 | 65.8 | 0.153 | 6189 |
3 x 150 | 14.3 | 5.50 | 3.20 | 68.8 | 0.124 | 7131 |
3 x 185 | 16.0 | 5.50 | 3.30 | 72.7 | 0.0991 | 8387 |
3 x 240 | 18.3 | 5.50 | 3.50 | 78.1 | 0.0754 | 10308 |
3 x 300 | 20.5 | 5.50 | 3.60 | 83.1 | 0.0601 | 12316 |
3 x 400 | 23.2 | 5.50 | 3.90 | 89.4 | 0.0470 | 15050 |
CU/XLPE/PVC, 1 COPPER LEAD, UNARRABLE 12/20 (24) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 5.50 | 1.80 | 25.2 | 0.524 | 878 |
1 x 50 | 8.2 | 5.50 | 1.80 | 26.3 | 0.387 | 1022 |
1 x 70 | 9.8 | 5.50 | 1.90 | 28.1 | 0.268 | 1263 |
1 x 95 | 11.6 | 5.50 | 1.90 | 29.9 | 0.193 | 1557 |
1 x 120 | 13.0 | 5.50 | 2.00 | 31.5 | 0.153 | 1824 |
1 x 150 | 14.3 | 5.50 | 2.00 | 32.8 | 0.124 | 2113 |
1 x 185 | 16.0 | 5.50 | 2.10 | 34.6 | 0.0991 | 2496 |
1 x 240 | 18.3 | 5.50 | 2.20 | 37.1 | 0.0754 | 3084 |
1 x 300 | 20.5 | 5.50 | 2.20 | 39.5 | 0.0601 | 3701 |
1 x 400 | 23.2 | 5.50 | 2.30 | 42.4 | 0.0470 | 4541 |
1 x 500 | 26.3 | 5.50 | 2.40 | 45.7 | 0.0366 | 5614 |
1 x 600 | 28.8 | 5.50 | 2.50 | 48.4 | 0.0305 | 6581 |
1 x 630 | 29.9 | 5.50 | 2.60 | 49.5 | 0.0283 | 7024 |
CU/XLPE/PVC/DSTA/PVC, 3 COPPER LEADERS, STEEL TAPE Armor 12/20 (24) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of steel tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 5.50 | 0.50 | 2.80 | 57.8 | 0.524 | 4462 |
3 x 50 | 8.2 | 5.50 | 0.50 | 2.90 | 60.5 | 0.387 | 5040 |
3 x 70 | 9.8 | 5.50 | 0.50 | 3.00 | 64.5 | 0.268 | 5962 |
3 x 95 | 11.6 | 5.50 | 0.50 | 3.20 | 68.6 | 0.193 | 7066 |
3 x 120 | 13.0 | 5.50 | 0.50 | 3.30 | 72.1 | 0.153 | 8060 |
3 x 150 | 14.3 | 5.50 | 0.50 | 3.40 | 75.2 | 0.124 | 9107 |
3 x 185 | 16.0 | 5.50 | 0.50 | 3.50 | 79.2 | 0.0991 | 10500 |
3 x 240 | 18.3 | 5.50 | 0.50 | 3.70 | 86.1 | 0.0754 | 13496 |
3 x 300 | 20.5 | 5.50 | 0.50 | 3.90 | 91.3 | 0.0601 | 15742 |
3 x 400 | 23.2 | 5.50 | 0.50 | 4.10 | 97.9 | 0.0470 | 18790 |
CU/XLPE/PVC/DATA/PVC, 1 COPPER LEAD, 12/20 (24) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of Aluminium tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 5.50 | 0.50 | 1.90 | 30.1 | 0.524 | 1237 |
1 x 50 | 8.2 | 5.50 | 0.50 | 2.00 | 31.3 | 0.387 | 1400 |
1 x 70 | 9.8 | 5.50 | 0.50 | 2.00 | 33 | 0.268 | 1664 |
1 x 95 | 11.6 | 5.50 | 0.50 | 2.10 | 34.9 | 0.193 | 1982 |
1 x 120 | 13.0 | 5.50 | 0.50 | 2.10 | 36.4 | 0.153 | 2269 |
1 x 150 | 14.3 | 5.50 | 0.50 | 2.20 | 37.8 | 0.124 | 2575 |
1 x 185 | 16.0 | 5.50 | 0.50 | 2.20 | 39.6 | 0.0991 | 2985 |
1 x 240 | 18.3 | 5.50 | 0.50 | 2.30 | 42.2 | 0.0754 | 3615 |
1 x 300 | 20.5 | 5.50 | 0.50 | 2.40 | 44.7 | 0.0601 | 4272 |
1 x 400 | 23.2 | 5.50 | 0.50 | 2.50 | 47.7 | 0.0470 | 5166 |
1 x 500 | 26.3 | 5.50 | 0.50 | 2.60 | 51.1 | 0.0366 | 6298 |
1 x 600 | 28.8 | 5.50 | 0.50 | 2.70 | 53.9 | 0.0305 | 7320 |
1 x 630 | 29.9 | 5.50 | 0.50 | 2.70 | 55.1 | 0.0283 | 7784 |
CU/XLPE/PVC/SWA/PVC, 3 COPPER LEADERS, STEEL FIBER Armor 12/20 (24) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of steel wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 5.50 | 2.50 | 2.90 | 59.4 | 0.524 | 5913 |
3 x 50 | 8.2 | 5.50 | 2.50 | 3.00 | 62.1 | 0.387 | 6556 |
3 x 70 | 9.8 | 5.50 | 2.50 | 3.10 | 66.0 | 0.268 | 7596 |
3 x 95 | 11.6 | 5.50 | 2.50 | 3.30 | 70.2 | 0.193 | 8814 |
3 x 120 | 13.0 | 5.50 | 3.15 | 3.40 | 75.0 | 0.153 | 10798 |
3 x 150 | 14.3 | 5.50 | 3.15 | 3.50 | 78.1 | 0.124 | 11909 |
3 x 185 | 16.0 | 5.50 | 3.15 | 3.70 | 82.1 | 0.0991 | 13472 |
3 x 240 | 18.3 | 5.50 | 3.15 | 3.80 | 87.7 | 0.0754 | 15787 |
3 x 300 | 20.5 | 5.50 | 3.15 | 4.00 | 92.9 | 0.0601 | 18188 |
3 x 400 | 23.2 | 5.50 | 3.15 | 4.20 | 99.5 | 0.0470 | 21415 |
CU/XLPE/PVC/AWA/PVC, 1 COPPER LEAD, ALUMINUM FIBER Armor 12/20 (24) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of aluminium wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 5.50 | 1.60 | 2.00 | 30.8 | 0.524 | 1303 |
1 x 50 | 8.2 | 5.50 | 2.00 | 2.00 | 32.8 | 0.387 | 1552 |
1 x 70 | 9.8 | 5.50 | 2.00 | 2.10 | 34.6 | 0.268 | 1828 |
1 x 95 | 11.6 | 5.50 | 2.00 | 2.10 | 36.5 | 0.193 | 2157 |
1 x 120 | 13.0 | 5.50 | 2.00 | 2.20 | 38.0 | 0.153 | 2450 |
1 x 150 | 14.3 | 5.50 | 2.00 | 2.20 | 39.3 | 0.124 | 2763 |
1 x 185 | 16.0 | 5.50 | 2.00 | 2.30 | 41.2 | 0.0991 | 3176 |
1 x 240 | 18.3 | 5.50 | 2.50 | 2.40 | 44.8 | 0.0754 | 3968 |
1 x 300 | 20.5 | 5.50 | 2.50 | 2.50 | 47.3 | 0.0601 | 4647 |
1 x 400 | 23.2 | 5.50 | 2.50 | 2.60 | 50.3 | 0.0470 | 5573 |
1 x 500 | 26.3 | 5.50 | 2.50 | 2.70 | 53.7 | 0.0366 | 6720 |
1 x 600 | 28.8 | 5.50 | 2.50 | 2.80 | 56.5 | 0.0305 | 7775 |
1 x 630 | 29.9 | 5.50 | 2.50 | 2.80 | 57.7 | 0.0283 | 8243 |
CU/XLPE/PVC, 3 COPPER LEADERS, UNARRATED 18/30 (36) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 8.00 | 3.00 | 63.9 | 0.524 | 4083 |
3 x 50 | 8.2 | 8.00 | 3.10 | 66.5 | 0.387 | 4620 |
3 x 70 | 9.8 | 8.00 | 3.20 | 70.3 | 0.268 | 5487 |
3 x 95 | 11.6 | 8.00 | 3.40 | 74.3 | 0.193 | 6527 |
3 x 120 | 13.0 | 8.00 | 3.50 | 77.6 | 0.153 | 7464 |
3 x 150 | 14.3 | 8.00 | 3.60 | 80.6 | 0.124 | 8456 |
3 x 185 | 16.0 | 8.00 | 3.70 | 84.5 | 0.0991 | 9775 |
3 x 240 | 18.3 | 8.00 | 3.80 | 89.9 | 0.0754 | 11785 |
3 x 300 | 20.5 | 8.00 | 4.00 | 94.9 | 0.0601 | 13877 |
3 x 400 | 23.2 | 8.00 | 4.20 | 101.2 | 0.0470 | 16724 |
CU/XLPE/PVC, 1 COLLECTOR, UNARRATED 18/30 (36) KV
Nominal area | Conductor diameter |
Thickness of insulation |
Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 8.00 | 1.90 | 30.6 | 0.524 | 1139 |
1 x 50 | 8.2 | 8.00 | 2.00 | 31.8 | 0.387 | 1297 |
1 x 70 | 9.8 | 8.00 | 2.00 | 33.5 | 0.268 | 1553 |
1 x 95 | 11.6 | 8.00 | 2.10 | 35.4 | 0.193 | 1863 |
1 x 120 | 13.0 | 8.00 | 2.10 | 36.9 | 0.153 | 2143 |
1 x 150 | 14.3 | 8.00 | 2.20 | 38.3 | 0.124 | 2443 |
1 x 185 | 16.0 | 8.00 | 2.20 | 40.1 | 0.0991 | 2842 |
1 x 240 | 18.3 | 8.00 | 2.30 | 42.6 | 0.0754 | 3451 |
1 x 300 | 20.5 | 8.00 | 2.40 | 44.9 | 0.0601 | 4087 |
1 x 400 | 23.2 | 8.00 | 2.50 | 47.9 | 0.0470 | 4957 |
1 x 500 | 26.3 | 8.00 | 2.60 | 51.2 | 0.0366 | 6058 |
1 x 600 | 28.8 | 8.00 | 2.70 | 53.8 | 0.0305 | 7043 |
1 x 630 | 29.9 | 8.00 | 2.70 | 55.0 | 0.0283 | 7496 |
CU/XLPE/PVC/DSTA/PVC, 3 COPPER LEADERS, 18/30 (36) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of steel tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 8.00 | 0.50 | 3.20 | 70.1 | 0.524 | 5891 |
3 x 50 | 8.2 | 8.00 | 0.50 | 3.30 | 72.8 | 0.387 | 6520 |
3 x 70 | 9.8 | 8.00 | 0.50 | 3.40 | 76.7 | 0.268 | 7517 |
3 x 95 | 11.6 | 8.00 | 0.80 | 3.60 | 82.2 | 0.193 | 9540 |
3 x 120 | 13.0 | 8.00 | 0.80 | 3.70 | 85.6 | 0.153 | 10632 |
3 x 150 | 14.3 | 8.00 | 0.80 | 3.80 | 88.7 | 0.124 | 11767 |
3 x 185 | 16.0 | 8.00 | 0.80 | 3.90 | 92.8 | 0.0991 | 13270 |
3 x 240 | 18.3 | 8.00 | 0.80 | 4.10 | 98.3 | 0.0754 | 15543 |
3 x 300 | 20.5 | 8.00 | 0.80 | 4.30 | 103.6 | 0.0601 | 17884 |
3 x 400 | 23.2 | 8.00 | 0.80 | 4.50 | 110.2 | 0.0470 | 21066 |
CU/XLPE/PVC/DATA/PVC, 1 COPPER LEAD, 18/30 (36) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Thickness of Aluminium tape armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 8.00 | 0.50 | 2.10 | 35.6 | 0.524 | 1573 |
1 x 50 | 8.2 | 8.00 | 0.50 | 2.10 | 36.8 | 0.387 | 1746 |
1 x 70 | 9.8 | 8.00 | 0.50 | 2.20 | 38.5 | 0.268 | 2025 |
1 x 95 | 11.6 | 8.00 | 0.50 | 2.30 | 40.4 | 0.193 | 2364 |
1 x 120 | 13.0 | 8.00 | 0.50 | 2.30 | 42.0 | 0.153 | 2671 |
1 x 150 | 14.3 | 8.00 | 0.50 | 2.40 | 43.5 | 0.124 | 2995 |
1 x 185 | 16.0 | 8.00 | 0.50 | 2.40 | 45.3 | 0.0991 | 3425 |
1 x 240 | 18.3 | 8.00 | 0.50 | 2.50 | 47.9 | 0.0754 | 4079 |
1 x 300 | 20.5 | 8.00 | 0.50 | 2.60 | 50.3 | 0.0601 | 4758 |
1 x 400 | 23.2 | 8.00 | 0.50 | 2.70 | 53.4 | 0.0470 | 5689 |
1 x 500 | 26.3 | 8.00 | 0.50 | 2.80 | 56.8 | 0.0366 | 6852 |
1 x 600 | 28.8 | 8.00 | 0.50 | 2.90 | 59.6 | 0.0305 | 7891 |
1 x 630 | 29.9 | 8.00 | 0.50 | 2.90 | 60.8 | 0.0283 | 8366 |
CU/XLPE/PVC/DATA/PVC, 1 COPPER LEAD, 18/30 (36) KV
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of steel wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
3 x 35 | 7.1 | 8.00 | 3.15 | 3.40 | 72.8 | 0.524 | 8528 |
3 x 50 | 8.2 | 8.00 | 3.15 | 3.50 | 75.5 | 0.387 | 9229 |
3 x 70 | 9.8 | 8.00 | 3.15 | 3.60 | 79.5 | 0.268 | 10397 |
3 x 95 | 11.6 | 8.00 | 3.15 | 3.70 | 83.6 | 0.193 | 11743 |
3 x 120 | 13.0 | 8.00 | 3.15 | 3.80 | 87 | 0.153 | 12919 |
3 x 150 | 14.3 | 8.00 | 3.15 | 3.90 | 90.1 | 0.124 | 14149 |
3 x 185 | 16.0 | 8.00 | 3.15 | 4.10 | 94.2 | 0.0991 | 15717 |
3 x 240 | 18.3 | 8.00 | 3.15 | 4.20 | 99.7 | 0.0754 | 18132 |
3 x 300 | 20.5 | 8.00 | 3.15 | 4.40 | 105.0 | 0.0601 | 20626 |
3 x 400 | 23.2 | 8.00 | 3.15 | 4.60 | 111.6 | 0.0470 | 23985 |
CU/XLPE/PVC/AWA/PVC, 1 COPPER LEAD, 18/30 (36) KV ALUMINUM FIRST
Nominal area | Diameter of conductor |
Thickness of insulation |
Diameter of aluminium wire armoured | Thickness of outer sheath |
Approx. overall diameter |
DC resistance at 200C |
Approx. mass of cable |
(mm2) | (mm) | (mm) | (mm) | (mm) | (mm) | (Ω/km) | (Kg/km) |
1 x 35 | 7.1 | 8.00 | 2.00 | 2.20 | 37.0 | 0.524 | 1739 |
1 x 50 | 8.2 | 8.00 | 2.00 | 2.20 | 38.2 | 0.387 | 1920 |
1 x 70 | 9.8 | 8.00 | 2.00 | 2.30 | 40.0 | 0.268 | 2211 |
1 x 95 | 11.6 | 8.00 | 2.00 | 2.30 | 41.9 | 0.193 | 2561 |
1 x 120 | 13.0 | 8.00 | 2.50 | 2.40 | 44.5 | 0.153 | 3020 |
1 x 150 | 14.3 | 8.00 | 2.50 | 2.50 | 46.0 | 0.124 | 3360 |
1 x 185 | 16.0 | 8.00 | 2.50 | 2.50 | 47.8 | 0.0991 | 3803 |
1 x 240 | 18.3 | 8.00 | 2.50 | 2.60 | 50.4 | 0.0754 | 4477 |
1 x 300 | 20.5 | 8.00 | 2.50 | 2.70 | 52.8 | 0.0601 | 5178 |
1 x 400 | 23.2 | 8.00 | 2.50 | 2.80 | 55.9 | 0.0470 | 6127 |
1 x 500 | 26.3 | 8.00 | 2.50 | 2.90 | 59.3 | 0.0366 | 7318 |
1 x 600 | 28.8 | 8.00 | 2.50 | 3.00 | 62.1 | 0.0305 | 8376 |
1 x 630 | 29.9 | 8.00 | 2.50 | 3.00 | 63.3 | 0.0283 | 8868 |